Skip to main content

2-way flanged valve, PN 40 (el.)

VUS

How energy efficiency is improved

Efficiency means precise and reliable control


Features

  • Continuous control of cold, warm and hot water in closed circuits, and of steam

  • In combination with valve actuators AVM 322(S), AVM 234S and AVF 234S as control unit

  • Water quality as per VDI 2035

  • Not suitable for drinking water

  • Valve with flange connection as per EN 1092-2, seal form B

  • Regulating valve, free of silicone grease, matt black

  • Equal-percentage characteristic, can be set with SUT valve actuators to linear or quadratic

  • The valve is closed when the spindle is moved in. Closing procedure only against the pressure

  • Valve body made of cast steel; spindle, seat and plug of stainless steel

  • Maintenance-free stuffing box, made of stainless steel, with spring-loaded PTFE washer up to 220 °C, with graphite seal up to 260 °C

 Product search
© 2024  Fr. Sauter AG All rights reserved

SAUTER Head Office was the target of a cyber security incident on November 20, 2024. SAUTER’s IT department immediately activated, well defined, internal emergency plans. All IT systems were completely isolated and shut down to successfully prevent the attack from spreading. External cybersecurity experts and data forensics specialists then began to check all systems and restore them securely. This process is unfortunately time-consuming, but absolutely necessary to ensure that the cyber-attack does not continue at a later date.


The SAUTER websites have been affected by the emergency operation and are available again with immediate effect.


There are currently no concrete indications that our customers' infrastructures have been compromised in any way by SAUTER devices. It appears to be an opportunistic incident with no clearly recognisable long-term goals or systematic attacks. The situation does not currently suggest that there is a targeted, sustained threat to the affected systems.